Cast iron swing check valves with counter weight and lever PN 10 and 16

Valvotubi fig.111 swing check valve with counterweight lever
Article: 111
Face to face length: EN 558-1 serie 48, DIN 3202 F6
Flanges UNI EN 1092-2 PN 10 - 16
Installation: horizontal / vertical with down-up flow direction
APPLICATIONS • Water supply • Pumping stations • Wastewater treatment plants • Hydropower plants • Sewage

- Fig. 110: without counterweight lever, PN 10
- Fig. 113: without counterweight lever, PN 16
Epoxy paiting suitable for drinking water applications.

The swing check valves with counter weight and lever grant a good performance of the anti-hammer effect thanks to the presence of the counter weight, that acts automatically when the flow stops. These swing check valves can be applied for both horizontal and vertical installations. For installation in vertical flow lines, we recommend to turn the counterweight 90° clockwise, so that, when the valve is ready for use, the counterweight will be in horizontal position.

 

Materials
body cast iron GG25, EN-GJL-250
cover cast iron GG25, EN-GJL-250
swing cast iron GG25, EN-GJL-250
body seat facing  brass
disc seat facing  rubber / brass
gasket  asbestos free
pin stainless steel X 20 CR 13 / brass
painting  epoxy
 
DN L mm. H mm. D mm. Weight kg.
 50  200  130  165  11
 65  240  155  185  14.2
 80  260  170  200  17.8
 100  300  200  220  24
 125  350  225  250  43
 150  400  240  285  58
 200  500  280  340  98
 250  600  330  395  140
 300  700  360  445  192
 350  800  410  505  255
 400  900  450  565  350
450 1000 480 615 560
500 1100 590 670 700
600 1300 680 780 960
DN Nominal pressure Test pressure Mpa Max working pressure Mpa
mm BAR body seat 80°C
50-600 16 2,4 1,76 1,6
50-600 10 1,5 1,1 1,0