Article: 111
Face to face length: EN 558-1 serie 48, DIN 3202 F6
Flanges UNI EN 1092-2 PN 10 - 16
Installation: horizontal / vertical with down-up flow direction
APPLICATIONS • Water supply • Pumping stations • Wastewater treatment plants • Hydropower plants • Sewage
- Fig. 110: without counterweight lever, PN 10
- Fig. 113: without counterweight lever, PN 16
Epoxy paiting suitable for drinking water applications.
The swing check valves with counter weight and lever grant a good performance of the anti-hammer effect thanks to the presence of the counter weight, that acts automatically when the flow stops. These swing check valves can be applied for both horizontal and vertical installations. For installation in vertical flow lines, we recommend to turn the counterweight 90° clockwise, so that, when the valve is ready for use, the counterweight will be in horizontal position.
Materials
body |
cast iron GG25, EN-GJL-250 |
cover |
cast iron GG25, EN-GJL-250 |
swing |
cast iron GG25, EN-GJL-250 |
body seat facing |
brass |
disc seat facing |
rubber / brass |
gasket |
asbestos free |
pin |
stainless steel X 20 CR 13 / brass |
painting |
epoxy |
DN |
L mm. |
H mm. |
D mm. |
Weight kg. |
50 |
200 |
130 |
165 |
11 |
65 |
240 |
155 |
185 |
14.2 |
80 |
260 |
170 |
200 |
17.8 |
100 |
300 |
200 |
220 |
24 |
125 |
350 |
225 |
250 |
43 |
150 |
400 |
240 |
285 |
58 |
200 |
500 |
280 |
340 |
98 |
250 |
600 |
330 |
395 |
140 |
300 |
700 |
360 |
445 |
192 |
350 |
800 |
410 |
505 |
255 |
400 |
900 |
450 |
565 |
350 |
450 |
1000 |
480 |
615 |
560 |
500 |
1100 |
590 |
670 |
700 |
600 |
1300 |
680 |
780 |
960 |
DN |
Nominal pressure |
Test pressure Mpa |
Max working pressure Mpa |
mm |
BAR |
body |
seat |
80°C |
50-600 |
16 |
2,4 |
1,76 |
1,6 |
50-600 |
10 |
1,5 |
1,1 |
1,0 |